background image

731.9

[28.8]

637.6

[25.1]

LEFT SIDE VIEW

642

[25.3]

76.2 [3.0]

PEA GRAVEL

MINIMUM

TRANSFER

SWITCH

8KW - 17KW

(IF SUPPLIED)

TRANSFER

SWITCH

20KW

(IF SUPPLIED)

1218

[47.9]

FRONT VIEW

1226

[48.3]

H2

H1

W1

W2

H2

H1

W1

W2

Generac

®

Guardian

®

Series Standby Generator - 20 kW

Design and specifications subject to change without notice. Dimensions shown are approximate. Contact your Generac dealer for certified drawings. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.

®

Transfer Switch Features

• Includes Digital Load Management technology standard (DLM).

• Intelligently manages two air conditioner loads with no additional hardware.

• Up to four more large (240V) loads can be managed when used in

conjunction with DLM modules.

• Electrically operated, mechanically-held contacts for fast, clean

connections.

• Rated for all classes of load, 100% equipment rated, both inductive and

resistive.

• Dual coil design.

• Service Rated.

• NEMA 3R aluminum outdoor enclosure.

• Main contacts are silver plated or silver alloy to resist welding and sticking.

TRANSFER SWITCH

Model 005875-1

No. of Poles

2

Current Rating (amps)

200

Voltage Rating (VAC)

250

Utility Voltage Monitor (fixed)
-Pick-up
-Dropout

80%
60%

Return to Utility

approx. 13 sec.

Exerciser weekly for 12 minutes

Standard

UL Listed

Standard

Enclosure Type

NEMA 3R

Withstand Rating (Amps)

10,000

Lug Range

400MCM - #4

H2

DEPTH

H1

W2

W1

200 Amps 120/240, 1ø

Open Transition Service Rated

Height

Width

Depth

H1

H2

W1

W2

Inches 27.24

30.0

11.4

13.5

7.09

mm 692.0

762.4

289.0

343.0

180.0

Advertising