Advanced programming – GE GNPR40L User Manual

Page 22

Advertising
background image

Advanced programming and troubleshooting section.

WARNING:

Advanced programming should

only be performed by a qualified technician.

This section was designed for the use of water treatment
professionals. Default settings are based on water conditions
at a typical installation. Before making any changes, consult
a water treatment professional, as incorrect settings may
result in a system malfunction. Programming the control is
not covered under the warranty.

To access advanced programming, simultaneously hold down
the UP and DOWN buttons. This will allow you to enter
advanced programming settings P6 through P19 (see table
below).

Advanced Programming Parameters

Minimum

Units

Parameter

Description

Range

Increments

of Measure

Notes

P6

Refill controller

1–99

1

gpm

0.33 gpm, both models

P7

Brine draw value

1–99

1

Minutes

40L – 15 and 48L – 16

P8

Not used

N/A

N/A

N/A

N/A

P9

Backwash time

3–30

1

Minutes

Skip this parameter to accept the default
or enter a value.

P10

Slow rinse time

8–125

1

Minutes

GNPR40L = 67
GNPR48L = 83

P11

Fast rinse time

2–19

1

Minutes

Skip this parameter to accept the default
or enter a value.

P12

Units of measure

0–1

1

0 = U.S.
1 = Metric
Skip this parameter to accept the default
(U.S.).

P13

Clock mode

0–1

1

0 = 12-hour clock
1 = 24-hour clock
Skip this parameter to accept the default
(12-hour).

P14

Calendar override

0–30

1

days

0 = no calendar override
Skip this parameter to accept the default
(no override).

P15

Reserve type

0–3

1

0 = variable reserve

P16

Fixed reserve capacity

0–70

1

percent of capacity

Description depends on the value

or initial average value

entered for P15 (Reserve type). Skip this
parameter to accept the default.

P17

Operation type

0–1

1

0 = Not used
1 = 5-cycle counter current

P18

Salt/capacity change

0–1

1

0 = None

lock out

1 = salt/capacity change locked out
Skip this parameter to accept the default
(no lock out).

P19

Factory defaults

DO NOT

1

Loads in factory default values. DO NOT

CHANGE

CHANGE THIS PARAMETER.

22