Rough-In Dimensions

Dryer MUST be exhausted outside (outdoors,

not beneath the mobile home) using metal

ducting that will not support combustion. Metal

ducting must be 4

(10.16 cm) in diameter with

no obstructions. Rigid metal duct is preferred.
If dryer is exhausted through the floor and area

beneath the mobile home is enclosed, the

exhaust system MUST terminate outside the

enclosure with the termination securely fastened

to the mobile home structure.
When installing a gas dryer into a mobile home,

a provision must be made for outside make-up

air. This provision is to be not less than twice the

area of the dryer exhaust outlet.
This dryer MUST be fastened to the floor. Mobile

Home Installation Kit Pub. No. 14-D346-33 is

available from your dealer.
See the Exhaust System Requirements