Ballast System—

All Ultra

Sport floodlights feature the new

compact GE Accuwatt

TM

ballast system in which the ballast is

direct mounted to the aluminum housing with a thermal wedge
for optimum heat transfer.

GE Accuwatt

TM

2000, 1500 and 1000 watt auto-regulator circuits

are designed to start and stabilize their respective double-ended
metal halide lamps at their design center.

Ballast dielectric material is rated for a 200 degree C maximum

operating temperature.

Every ballast undergoes a 2500 volt RMS “High Pot” and a

10KV “til” test in accordance with ANSI C82.4, C82.6 and C92.1
specifications. The ballast circuits are also designed to sustain a
nominal lamp over a line voltage dip of 50% for up to four
seconds when operating at nominal line voltage according to
ANSI specification C82.6.

Ultra

Sport

TM

Floodlight

e

Optional System 2

TM

Bi-Level Controls—

The choice of

high/low two-level lighting is also available. System 2 Bi-Level
controls utilize a 15 volt AC signal that is hard wired to the
floodlight to switch capacitance and change wattage.

The 2000/1500 watt and 1500/1000 watt system choices are

available for separate game time and practice light levels.

The ballast circuit will reliably start and stabilize a

nominal lamp in ambient temperatures down to -29
degrees C. The unit is rated for operation in up to
40 degree C ambient temperatures.*

Ballast Maintenance—

Electrical access is

achieved from the rear of the fixture without any
adjustment to the aiming required. The rear
housing cover is held in place by four captive
corrosion-resistant cad-polymer coated screws.

Optional Instant Hot Restart—

The

Ultra

Sport floodlight can be ordered with a new

optional instant hot restart feature. After a
momentary power interruption or line voltage dip
which causes the lamp to extinguish, a 34KV hot
restart circuit will restart the lamp within two
seconds of re-application of power.

% Allow-
able Line

Line

Power

Line

% Allow-

Line

Voltage

Operating

Line

Factor

Starting

able Line

Watts

Volts

Variation

Amperes

Watts %

Amperes

Voltage Dip

2000

208

11.2

2125

10.0

*25°C

240

9.5

2115

8.5

Max

277

8.3

2115

7.2

Ambient 347

±10

6.6

2122 90+

5.6

50

480

4.8

2132

4.4

1500

120

14.4

1630

11.2

*40°C

208

8.5

1630

6.9

Max

240

7.3

1630

5.6

Ambient 277

±10

6.3

1630 90+

4.7

50

347

4.8

1620

3.9

480

3.7

1630

2.8

1000

120

9.0

1080

6.6

*40°C

208

5.4

1070

4.1

Max

240

±

4.8

1080 90+

3.5

50

Ambient 237

4.1

1080

2.9

347

3.6

1070

2.9

480

2.6

1088

1.8

NOTE: For 50Hz voltages, contact factory.
*See ballast table for wattage limitations.