Generac 005030-0 User Manual

Page 14

Advertising
background image

12

2.10 ENGINEERED TRANSFER SWITCH

(2-WIRE START GTS MODE)

When required, the pre-packaged standby generator
can be installed with an engineered W Type transfer
switch which controls utility voltage sensing, weekly
exercising and load transferring.

When Position 2 of the eight-position DIP switch,
which is located on the generator circuit board (See
Figure 3.2), is in the ON position then utility voltage
sensing, weekly exercising and load transferring is
under the control of the Engineered W Type transfer
switch (GTS Mode).

Generator DIP Switch Position 2 ON = 2-Wire Start
GTS Mode

• The generator control board will NOT monitor the

utility.

• The generator control board will NOT perform a

weekly exercise. (The five red LEDs will flash one
at a time in GTS mode.)

• The generator control board will NOT activate the

transfer output.

The generator control board WILL monitor all engine
conditions and shut down on all the faults listed in
this document.

For the W Type transfer switch to control utility volt-
age sensing, weekly exercising and load transferring,
suitable wiring must also be connected from the
transfer switch 178 and 183, 2-Wire Start terminals
to the corresponding generator 178 and 183 2-Wire

Start terminals. Recommended wire gauge sizes for
the 2-Wire Start wiring depend on the length of the
wire (see wiring length chart).

Route the 2-Wire Start control wires through suitable,
approved conduit which is separate from the AC
power leads. Connection of wire 178 to wire 183 by
relay contact closure action (volt free switch contacts)
in the transfer switch must result in generator engine
cranking and startup (See Figure 2.4).

Do NOT connect battery voltage, utility voltage
(N1/N2) or load voltage (T1/T2) to either the
178 or the 183 2-Wire start terminals as this will
damage the generator control board.

In order for the generator battery charging function to
work, it is necessary to provide a 5 amp fused 240Vac
utility source connection from the transfer switch
main N1 and N2 terminals to the generator control
panel N1 and N2 terminals (See Figure 2.4).

!

FROM UTILITY

TO LOAD

FEEDER CIRCUITS

LOAD

DISTRIBUTION

PANEL

GENERATOR

194

23

178

183

N2 N1

E1 E2

E1 E2

178

183

N1 N2

N1
N2

FUSE

FUSE

W-TYPE

TRANSFER

SWITCH

T1
T2

MAIN LINE

CIRCUIT

BREAKER

OR FUSE

Figure 2.4 - Connection Diagram (GTS Mode)

MAXIMUM WIRE LENGTH

RECOMMENDED WIRE

SIZE

460 feet (140m)

No. 18 AWG.

461 to 730 feet (223m)

No. 16 AWG.

731 to 1,160 feet (354m)

No. 14 AWG.

1,161 to 1,850 feet (565m)

No. 12 AWG.

Section 2 — Installation

Liquid-cooled 15, 20 and 25 kW Generators

Advertising
This manual is related to the following products: