4 manual retransfer and shutdown, 5 automatic operation, 6 weekly exercise cycle – Generac 005030-0 User Manual

Page 19

Advertising
background image

17

6. Reduce load to 3/4, 1/2, 1/4 and no load.

Decrease the stability pot if there is instability at
any load point.

7. Adjust differential pot to make the recovery to

load changes even faster and minimize load
change undershoot and overshoot. If it is set too
high, it may introduce oscillations at some load.
It can be set to zero (full CCW) if a small amount
causes oscillations at some load.

8. Leave DIP switch 8 in TEST mode.

3.4

MANUAL RETRANSFER AND
SHUTDOWN

When utility power source voltage has been restored,
electrical loads may be transferred back to that
source and the generator can be shut down as fol-
lows:

• Verify that utility power supply voltage to the trans-

fer switch has been positively turned Off, using
whatever means provided (such as utility main line
circuit breaker).

• Set the generator’s main circuit breaker to its Off

or Open position.

• Let the generator engine run at no-load for a few

minutes, to stabilize internal unit temperatures.

• On the generator console, set the Auto/Off/ Manual

switch to Off. Wait for engine to come to a complete
stop.

• For transfer to utility position, refer to the Owner’s

Manual of the particular transfer switch.

• Turn on the utility power supply to the transfer

switch, using whatever means provided (such as a
utility main line circuit breaker). The utility power
source now powers the loads.

3.5

AUTOMATIC OPERATION

To set the system for fully automatic operation, pro-
ceed as follows:

• Check that load circuits are connected to the

utility power supply.

• Set the AUTO/OFF/MANUAL switch to its AUTO

position.

• Set the generator main circuit breaker to its ON or

CLOSED position.

3.6

WEEKLY EXERCISE CYCLE

The engine control board will start and run the gen-
erator once every seven days for approximately 12
minutes. If utility should fail during this exercise
period, the engine control board will transfer the load
to the generator output and continue to run until util-
ity returns.

On the day, and at the time of day chosen for the gen-
erator to exercise, set the weekly exercise cycle as fol-
lows:

1. Place the AUTO/OFF/MANUAL switch in the

AUTO position (Figure 3.3).

2. Press and hold the “Set Exercise Time” switch for

five seconds, then release.

At this time all five red LEDs will flash for approxi-
mately 10 seconds, then the engine will start and run
for it’s 12 minute exercise period, then shut down.
The generator will now start and run each week at the
same time.

Figure 3.3 - “Set Exercise Time” Switch

If DC power to the control board is lost, the weekly
exercise setting will be lost. This is indicated by all
five red LEDs continually flashing. In this state the
generator will still start and run in MANUAL mode,
or automatically start and run if utility is lost while in
AUTO mode, but it will not perform a weekly exercise
cycle.

If a failure occurs while running in this mode, the five
red LEDs will stop flashing, the individual fault LED
will turn on and the engine will shut down. Once the
AUTO/OFF/MANUAL switch has been switched to
OFF, the individual fault LED will turn OFF and the
five red LEDs will begin flashing to show exercise has
still not been set.

ON

0

THEN THE UNIT WILL START, RUN THROUGH THE EXERCISE CYCLE AND SHUTDOWN.

MANUAL

SET

EXERCISE

TIME

TO SET EXERCISER TIME

2) HOLD "SET EXERCISE TIME" SWITCH IN "ON" POSITION FOR THREE SECONDS
AND RELEASE. (SEE OWNER'S MANUAL FOR COMPLETE DETAILS)
THE EXERCISER IS NOW SET. ALL FIVE RED LED'S WILL FLASH FOR 10 SECONDS

1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.

AUTO

OFF

RED LED'S = INDIVIDUAL FAULT

OFF

(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)

SOLID GREEN LED SYSTEM READY, UTILITY POWER ON

Section 3 - Operation

Liquid-cooled 15, 20 and 25 kW Generators

Advertising
This manual is related to the following products: