OPERATING DATA

GR160

STANDBY

PRIME

GR160

GR160

GENERATOR OUTPUT VOLTAGE/KW-60HzSTANDBY

240V, 1-phase, 1.0 pf

kW

133

126

120/208V, 3-phase, 0.8 pf

kW

133

126

139/240V, 3-phase, 0.8 pf

kW

133

126

277/480V, 3-phase, 0.8 pf

kW

133

126

AMPERAGE

Single phase 240V

Amps

554

525

Three phase 208V

Amps

461

437

Three phase 240V

Amps

400

379

Three phase 480V

Amps

200

189

MOTOR STARTING KVA

416V

480V

416V

480V

Maximum at 35% instantaneous voltage dip

60 Hz - kVA

680

950

680

950

FUEL

Fuel consumption 60 Hz

Load

25%

50%

75%

100%

25% 50% 75% 100%

gal/hr

4.4

6.6

8.8

9.3

3.5

5.3

7.0

7.4

liters/hr

16.7

25.0

33.3

35.2

13.4

20.0

26.6 28.2

COOLING

Coolant capacity

System lit (US gal)

22 (5.8)

22 (5.8)

Engine lit (US gal)

14 (3.7)

14 (3.7)

Radiator lit (US gal)

8 (2.1)

8 (2.1)

Coolant flow/min.

60 Hz - lit (US gal)

270 (71.3)

270 (71.3)

Heat rejection to coolant

BTU/hr

344,000

309,600

Inlet air

60 Hz - cu meters/min (cfm)

120 (4500)

120 (4500)

Max. inlet air temperature

°F

110

110

COMBUSTION AIR REQUIREMENTS

Flow at rated power

60 Hz - cu meters/min (cfm)

8.9 (314)

8.0 (283)

EXHAUST

Exhaust flow at rated output 60 Hz cu meters/min (cfm)

31.6 (1115)

28.4 (1003)

Maximum recommended back pressure Kpa ("H

2

O)

7.5 (30)

7.5 (30)

Exhaust temperature at rated output

°C (°F)

496 (925)

446 (835)

ENGINE

Rated RPM

60 Hz

1800

1800

Rated HP

60 Hz

194

175

Piston speed

60 Hz - m/min (ft/min)

464 (1524)

464 (1524)

BMEP (psi)

60 Hz

171

155

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

Temperature

-3% for every 10°C above - °C

25

25

-1.5% for every 10°F above - °F

77

77

Attitude

-3.0% for every 300 m above - m

1523

1523

-3.0% for every 1000 ft above - ft

5000

5000