HARDWARE

GEK-106465A

CIO Remote CAN Digital I/O Module

21

The following lines describe the different types of connection to create each scheme in an easy way. As the
supervision circuits are identical, we will describe connection examples for the first group. They are also applicable to
the second group.

The symmetrical location of digital inputs is an optimization for ensuring a high isolation between groups that,
belonging to different groups could be connected to separate batteries, and therefore a greater distance between
circuits is required.

3.4.2.1. WITHOUT

SUPERVISION

This is a very frequent case, and we must only wire the tripping circuit to terminals 35 and 36, leaving unused
terminals 34, 15, 16, 17, 18.

FIGURE 3-8 CIRCUIT WITHOUT TRIPPING CIRCUIT SUPERVISION (A6631F1)