Drawing 1b, Piping, Fig. 5-4 – Munchkin 399M User Manual

Page 22

Advertising
background image

22

PIPING

Standard Munchkin boiler
Retrofit piping (zoning with valves)

Domestic water heating mode

Munchkin boiler

P1

Super Stor

indirect DHW tank

T/P

Drawing 1B

make-up water

purging

valves

V1

zone valves

flow

bypass

valve

anti-scald

mixing valve

NOTES:

1.

This drawing is meant to show system piping concept only.
Installer is responsible for all equipment & detailing required by local codes.

2.

Adjust flow bypass valve for the following minimum boiler flow rates in any operating mode:

Munchkin model 399M: 16 gpm

3.

The minimum pipe size for connecting a Super Stor water heater is 1 inch.

4.

The minimum pipe size for connecting a Munchkin boiler is 2.00 inches.

5.

All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.

6.

The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.

7.

Install a minimum of 12 diameters of straight pipe upstream of all circulators.

8.

A purging valve may be used in lieu of the ball valve / hose bib combination shown

.

cold

water

OFF

OFF

OFF

OFF

Fig. 5-4

Advertising