Refrigerant system diagram 9, Mxz-24uv - mxz-24uv – MITSUBISHI ELECTRIC MXZ-24UV User Manual

Page 11

Advertising
background image

11

REFRIGERANT SYSTEM DIAGRAM

9

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes,refer to the
tables below.

When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe,see page BACK COVER.

Indoor unit

Extension pipe diameter

class

Pipe diameter

Liquid

6.35(1/4)

Liquid

6.35(1/4)

07/09

Gas

9.52(3/8)

Gas

9.52(3/8)

Liquid

6.35(1/4)

Liquid

6.35(1/4)

12

Gas

12.7(1/2)

Gas

12.7(1/2)

Liquid

6.35(1/4)

Liquid

6.35(1/4)

18

Gas

15.88(5/8)

Gas

15.88(5/8)

Outdoor unit union diameter

For

Liquid

6.35(1/4)

Indoor unit A

Gas

12.7(1/2)

Liquid

6.35(1/4)

Indoor unit B

Gas

12.7(1/2)

Liquid

6.35(1/4)

Indoor unit C

Gas

9.52(3/8)

Unit : mm (inch)

Piping length each indoor unit (a, b, c)

25m

Total piping length (a+b+c)

50m

Height difference between units (H)

10m

Bending point for each unit

25

Total bending point

50

It does not matter which unit is higher.

a

b

c

Outdoor
unit

Indoor
units

H

H

H

Unit:mm

MXZ-24UV -
MXZ-24UV -

E2

E1

OB287--1.qxp 03.1.16 10:29 AM Page 11

Advertising
This manual is related to the following products: