General product specifications – Minuteman UPS XRT Series User Manual

Page 36

Advertising
background image

35

7. GENERAL PRODUCT SPECIFICATIONS

XRT600

(XRT600/2)

XRT1000

(XRT1000/2)

XRT1500

XRT2000

(XRT2000/2)

XRT2001

XRT2002

Acceptable input

volts

92-140v

(169-268v)

92-140v

(169-268v)

92-140v

N/A

92-140v

(169-268v)

176-278v

152v-267v

Output Voltage

(on-line) +/- 10%

120v

(230v)

120v

(230v)

120v

N/A

120v

(230v)

120v/240v

120/208v

Nominal input

frequency

60 Hz

(50 Hz)

60 Hz

(50 Hz)

60 Hz

N/A

60 Hz
50 Hz

60 Hz

60 Hz

Input protection

Reset-able circuit breaker

Frequency limits

(online)

60 Hz. +/- 3 Hz

(50 Hz. +/- 3 Hz. )

Transfer time

4 ms Typical

Max load

(VA/watts)

600 /600

1000 / 1000

1500 / 1500

2000 / 2000

2000 / 2000

2000 / 2000

On Battery

Output Voltage

120v

(230v)

120v

(230v)

120v (N/A)

120v (230v)

120v /

240v

120v /

208v

On Battery

frequency

60 Hz +/-0.1 Hz. Unless synchronized to utility during brownout.

(50 Hz +/- 0.1 Hz. Unless synchronized to utility during brownout)

On Battery

waveform

Low distortion sine wave

Protection

Over-current and short circuit protected: latching shutdown on overload

Surge energy

rating

480 joules: one time 10 to 1000

µ s waveform ( 120 VAC units )

Surge current

capability

6500A maximum: one time 8 to 20

µ s waveform (120 VAC units )

Surge response

time

0 Ns (instantaneous) normal mode, <5 Ns common mode

Surge volts let

thru

< .2%

Noise filter

Normal and common mode EMI /RFI suppression, 100 kHz to 10 MHz

Battery type

Spill proof, sealed, maintenance free, lead-acid

Typical battery

life

5 years

Typical recharge

time

4 hours for a single battery pack

Operating temp

0 to 40

°C (+32 to 104°F)

Operating &

storage relative

humidity

0 to 95% non-condensing

Storage

temperature

-15 to +45

°C (+5 to 113°F)

Operating

elevation

0 to 3000 meters ( 0 to 10,000 ft. )

Electromagnetic

immunity

IEC 801-2, 801-3, 801-4: Severity level 5

Audible noise

<45 dB @ 1 meter

Audible Alarm

On overload, On battery, Low battery warning, check fan

Communication

s port

DB-9 Minuteman standard

Advertising