Operation, Battery" tab, Output" tab "by-pass" tab – MGE UPS Systems 12 kVA User Manual

Page 22

Advertising
background image

Page 22 -

51033212EN/AC

3. Operation

"Battery" tab

Rated AC-power source voltage (see figure 1)

Rated AC-power source frequency

Tolerance for AC-power source frequency

Alarm threshold for overload

Restart inverter after short circuit

230 V

50 Hz

±

5%

100%

Disabled

200 V-208 V-220 V-240 V

60 Hz

±

1% to

±

10% , in 1% steps

0 to 100%, in 10% steps

Enabled (click to add check)

Personalizable function

"Battery test" intervals

"Low-battery shutdown warning" threshold

Charger

Default setting

Every day

20% remaining battery

backup time

Standard

Options

Once a week

Once a month

No test

40% remaining battery

backup time

CLA (2, 4 or 8 hours)

Fig. 1

Available power as a percentage
of the rated power

Voltage in V

Authorized voltage range for transfer to bypass

if fault or overload

Authorized frequency range for transfer to bypass

if fault or overload

Transfer to bypass if overload

Transfer to bypass following a fault, whatever

the conditions on the AC-power source

187 V to 265 V (for

230 V rated voltage)

±

10%

Enabled

Disabled

187 V to 265 V,

in 1V steps

±

1% to

±

10%, in 1% steps

Disabled (click to remove check)

Enabled (click to add check)

"Output" tab

"By-pass" tab

The value selected for the rated UPS voltage impacts on the power available at UPS output
(see the diagram below).

100%

95%

90%

66%

50%

84