VII. GAS SUPPLY

Figure 2-14 - Utility Connection Locations for Electric Ovens

2" (51mm)

cutout for

electrical supply

A. Gas Utility Rough-In Recommendations
The following gas system specifications are STRONGLY

RECOMMENDED. Deviating from these recommendations

may affect the baking performance of the oven.

Gas Meter

•

One or two oven cavities: 750 cfh meter

•

Three or four oven cavities: 1200 cfh meter

Gas Line

•

DEDICATED LINE from the gas meter to the oven

•

2-1/2" (63.5mm) pipe for natural gas

•

2" (50.8mm) pipe for propane

•

Maximum length: 200' (61m). Each 90° elbow equals 7'

(2.13m) of pipe.

CAUTION

DURING PRESSURE TESTING NOTE ONE OF THE FOLLOWING:
1. The oven and its individual shutoff valve must be discon-

nected from the gas supply piping system during any

pressure testing of that system at test pressure in excess

of 1/2 psi (3.45 kPa).
2. The oven must be isolated from the gas supply piping

system by closing its individual manual shutoff valve dur-

ing any pressure testing of the gas supply piping system at

test pressure equal to or less than 1/2 psi (3.45 kPa).

3. If incoming pressure is over 14” W.C. (35mbar), a sepa-

rate regulator MUST be installed in the line BEFORE the

individual shutoff valve for the oven.
WARNING:
To prevent damage to the control valve regula-

tor during initial turn- on of gas, it is very important to open

the manual shutoff valve very slowly.
After the initial gas turn-on, the manual shutoff valve must

remain open except during pressure testing as outlined in

the above steps or when necessary during service main-

tenance.

SECTION 2 - INSTALLATION

Strain-relief

fitting