Installation

Preparing the Site

Select the site that meets the following requirements:

Characteristic Requirement

Temperature 32 to 104˚F (0 to 40˚C)

Humidity

Maximum relative humidity of 90%, non-condensing

Condition

At least 1.8 meters (6 feet) to the nearest source of electromagnetic noise

Ventilation

Minimum 3 inches (0.25 feet) of clearance around the ventilation openings

Power Outlet Within 1.8 meters (6 feet) to the switch

Table 2: SP616DB / SP624DB Operating Requirements


Settling the Switch
z Mounted to 19-inch standard rack

Locate the accessories provided in the product package. Use the rack-mount brackets and
screws to install the switch into any EIA 19” standard rack.
Step 1: Attach the brackets to each side of the chassis.
Step 2: Apply the screws to each side and secure them tightly.
Step 3: Carefully position the switch into the rack.
Step 4: Align the brackets to the side holes on the rack and use rack screws to secure the
chassis with the rack.
Step 5: Proceed to the “Connecting to Power” section.


z Desktop or any flat surface

The switch can sit on desktop or any flat surface with adequate space and ventilation. If you
want to place it onto a shelf, make sure the shelf can withstand the weight of the switch.
Step 1: Simply put the switch on the desired place.
Step 2: Ensure the switch receives good ventilation.
Step 3: Proceed to the “Connecting to Power” section.

Installing the Module (optional)
Consult the following illustrations for installation.

Figure 3: Removal of cover plate Figure 4: Fiber module being installed

Step 1: Make sure the power is switched off. The module is not hot-swappable.

L It may cause electric shock or any possible damage to the switch if the power is not
switched off.