Regenerative

Power

Module

-

September

2010

144-45117-R3

Page 6 of 20

Voltage Display

A 10-LED Switch Level bar graph provides a visual display of the approximate bus voltage level
when the brake transistor turns on.

Simplified Switching Level Selection

An 8-position DIP switch provides transistor turn on switching level selection in 15 steps.

Link Setting

Adj Range

Volt/Step

330

256 – 400 VDC

16

495

384 - 600

24

660

512 - 800

32

Choose the appropriate setting for the voltage link set up and set the appropriate corresponding
DIP switch position on. All other DIP settings must be off.


Mode Switches

A 4-position DIP switch provides the following configuration selections:

DIP Position

Off Setting

On Setting

1

Enable Ext Intlk Disable Ext Intlk

2

Auto Reset

Remote Reset

3

2-Term Res

3-Term Res

4

Not Used

Not Used

The External Interlock may be used for the connection of a normally closed temperature switch
mounted at the power resistor.

Overheat Protection

The thermistor mounted on the heat sink is used to protect against failure caused by excessive
duty combined with excessive ambient temperatures. The unit is shut down when the heat sink
temperature exceeds 95° C.


24V Output for Fan

A +24V Fan output is available for supplemental cooling. The Fan output is capable of
delivering up to 5W for the addition of an external fan separately mounted from the RPM unit.
The output becomes active when the heat sink temperature exceeds 65° C.