OM-481 Page 19

5-2.

Example Of Remote Amperage Control

Set Switches

Adjust Remote Control

Set Percentage

Min = 55 A DC/CC

Percentage Of Range = 50%

Max = 90 A DC/CC (50% of 55 to 125)

In Example:

S-0774 / S-0769

Set Range

Min (55 A DC/CC)

Max (90 A DC/CC)

2

3

SECTION 6 – OPERATING AUXILIARY EQUIPMENT

6-1.

120 Volt Duplex GFCI Receptacles

Ref. ST-174 733

Y

If unit does not have GFCI recep-
tacles, use GFCI-protected exten-
sion cord.

1

120 V 20 A AC GFCI
Receptacle GFCI1

2

120 V 20 A AC GFCI
Receptacle GFCI2

Receptacles supply 60 Hz single-phase
power at weld/power speed.

3

Circuit Breakers CB1 And CB2

CB1 protects GFCI1 and CB2 protects
GFCI2 from overload. If CB1 or CB2 opens,
the receptacle does not work.

.

If a circuit breaker continues to open,
contact a Factory Authorized Service
Agent.

If a ground fault is detected, the GFCI Reset
button pops out and the circuit opens to dis-
connect the faulty equipment. Check for
damaged tools, cords, plugs, etc. con-
nected to the receptacle. Press button to re-
set receptacle and resume operation.

.

At least once a month, run engine at
weld/power speed and press Test but-
ton to verify GFCI is working properly.

4

Total Generator Power Output

Maximum output from each duplex recep-
tacle is 1.8 kVA/kW, and 3 kVA/kW from all
receptacles. Generator power is not af-
fected by weld output.

EXAMPLE: If 15 A is drawn from GFCI1,
only 10 A is available at GFCI2:

(120 V x 15 A) + (120 V x 10 A) = 3.0 kVA/kW

1

2

3

4