WR / WC Series Woodburning Fireplace

20014528

Hearth Installation

A hearth extension is required to protect a combustible
floor in front of the fireplace. Refer to Figure 23 for mini-
mum dimensions and mounting detail.
NOTe: Hearth extension must not cover the air
inlet opening of a fireplace.
The hearth extension described in Figure 23 must be a
durable noncombustible material with a minimum (total)
Rt value of 1.09; refer to Figure 24 for examples. The
overall height (above a combustible floor), depth and
width must be as indicated, with the extension centered
to the fireplace opening.
The top of insulation must be covered with a noncom-
bustible decorative covering or a piece of .018” mini-
mum sheet metal, to protect hearth extension material.
(Fig. 23)
Secure the hearth extension to the floor to prevent
shifting, using trim molding or other similar means at
three (3) outer edges. Seal crack between the fireplace
hearth and hearth extension with a noncombustible
material. (Figs. 23 and 25)

Minimum Wall Clearances

WITH

Noncombustible

Surround Facing

WITHOUT

Noncombustible

Surround Facing

Minimum Hearth Extension Dimensions

(for On-Site Construction)

G

H

G

J

Seal cracks

between the

fireplace

and hearth

extension with

noncombustible

material

Safety strips

must overlap

1/2" minimum

May install

noncombustible

decorative

covering

OR .018" min.

sheet metal

FIREPLACE

HEARTH

COMBUSTIBLE

FLOOR

MINIMUM

INSULATION

VALUE "R"

4" MIN.

FP594
SR/SC
11/20/97

FIREBOX

OPENING

A - Min. clearance
to combustible
perpendicular wall

B - Min. clearance
to combustible
perpendicular wall when
using noncombustible wall shield*

SIDE
WALL

SIDE
WALL

F**

C**

E

E

D

4" BRICK
(Example material)

Combustible material permitted within shaded area.

* Noncombustible wall shield requires 1" MHSC EH2416

insulation (minimum R Value = 1.85) between decorative
noncombustible rigid covering and combustible wall.
Minimum height and width is 40" x 40".
** Dimension/degree of angle will vary depending on thickness

of noncombustible surround facing.

4"

Shaded area starts

1/2" away from

edge of unit.

FP594

Fig. 23 Combustible side wall protection and hearth extension dimensions.

A

b

C

D

e

F

g

H

J

WR/WC400

16"

12"

48°

41°

18"

14"

7³⁄₄"

16"

48"

406 mm 305 mm

457 mm 356 mm 197 mm 406 mm 1219 mm

WR/WC500

20"

12"

42°

35°

18"

14"

11¹⁄₂"

20"

61¹⁄₂"

508 mm 305 mm

457 mm 356 mm 292 mm 508 mm 1562 mm

Side Wall Protection

Adjacent combustible side walls that are within the mini-
mum dimensions shown in Figure 23 of fireplace open-
ing must be protected with MHSC Wall Shield Model
SP40 or a specifically built wall shield described below.
The special wall shield design described in Figure 20 is
an alternate method of adding protection to side walls
and can be used in place of the SP40 with the same
wall clearances specified for the SP40. Rt must =1.85
minimum.

examples of wall shield insulation:

1. Manville - CERAFORM 126, K=.27,
1/2 inches thick

2.

MHSC

- EH2416, K = .458,

1 inch thick required.