7-2. Connecting To Optional AC Power Plant

Ref. 197 399 / 802 332-B

.

Do not weld while using optional ac
power plant.

.

Place Process/Contactor switch in
Weld Terminals Always On - Stick

position when using optional ac

power plant (see Section 6-3).

Single-Phase Generator Power
1

120/240 V 50 A Receptacle RC5

RC5 is connected to the optional ac

power plant and supplies 60 Hz single-

phase power at weld/power speed.

Maximum output from RC5 is 12 kVA/

kW. Power available at RC5 is reduced

when welding.
2

Supplementary Protector CB7

Supplementary protector CB7 protects

single-phase receptacle RC5 and the

load wires from overload. If CB7

opens, all generator ac output stops

and the receptacle does not work.
Three-Phase Generator Power

!

Stop engine.

!

Power and weld outputs are live

at the same time. Disconnect or

insulate unused cables.

.

Have qualified person install ac-

cording to circuit diagram and

Generator Power Guidelines (see

Section 16).

Remove power panel mounting

screws. Tilt panel forward.
3

Lead 93

4

Lead 92

5

Lead 91

6

Lead 42 (Circuit Grounding Lead)

7

Lead 90 (Neutral)

8

Isolated Neutral Terminal

9

Jumper Lead 42

10 Grounding Terminal
Jumper 42 is connected to lead 90 at

factory. Jumper 42 may be discon-

nected from neutral to meet applicable

electrical codes.
Lead 42 connects to front panel

Ground stud.
11 User-Supplied Leads
12 Supplementary Protector CB7

User Terminals

Connect user-supplied leads to termi-

nals on CB7 and to the isolated neutral

terminal and grounding terminal as

necessary.

.

Supplementary protector CB7 pro-
tects single-phase receptacle RC5

and the load wires from overload.

If CB7 opens, all ac power plant

output stops and the receptacle

does not work.

Reinstall power panel.

Tools Needed:

Volts

Amps

KVA/KW

Single

120/240

50
12

Three

240

48
20

60 Hz

Frequency

Engine Speed

1850 RPM

AC

Phase

1

Phase

3

Output

Lead 42 connects to GROUND stud on

front of unit.
Jumper 42 is connected to 90 at factory.

1

2

91

92

93

240V

120V

120V

240V

240V

1-Phase

3-Phase

3

4

5

6

7

8

9

10

11

12

Rear Of Panel

Three-Phase Power Connection

2

Single-Phase Power Connection

92

90

91

93

!

Close panel opening

if no connections are

made to power plant.

!

Close panel

opening if no

connections

are made to

power plant.

240V

Remove plug

before inserting

leads. Reinstall

bushing.