34007532EN/AA

3. Operation

Personalisable function

Rated UPS voltage

Frequency mode

Rated UPS frequency

UPS tolerance for AC-power

source frequency

Overload alarm threshold

UPS restart following short-circuit

Default setting

230 V

Autoselect

F = 50 Hz

F

±

5%

110%

Disabled

Options

200 V - 208 V - 220 V - 240 V - 250 V

Converter

60 Hz

F

±

1% to

±

10%, in 1% steps

0 to 110%, in 10% steps

Enabled (click to add check)

Personalisable function

Transfer to bypass if overload

Transfer to bypass following a fault, whatever the

conditions on the AC-power source

Default setting

Enabled

Disabled

Options

Disabled (click to remove check)

Enabled (click to add check)

"Output" tab

"Bypass" tab

3.5 UPS shutdown

Press button 16 (return to the OFF position).

The connected equipment is no longer supplied with power.

test

1

2

BYPASS

16