MITSUBISHI ELECTRIC 2033C SERIES UPS

TABLE 1.4 Rating of Contactors and Fuses

Component

Description

Component Rating @ 208V,3 phase, 60 Hz

UPS Rating (kVA)

7.5

10

15

20

30

40

50

CB1

AC Input Contactor

60A

100A

150A

150A

CB2

DC Input Contactor

60A

100A

150A

150A

CB3

Static Bypass Input

Contactor

60A 100A

150A

150A

52C

AC Output Contactor

60A 100A

150A

150A

FIU-W

AC Input Fuse

140A/660V

180A/600V

280A/660V 280A/660V

FBP,FBN

Battery Input Fuse

140A/660V

180A/600V

280A/660V 280A/660V

FOU-W

AC Output Fuse

140A/660V 180A/600V

280A/660V

280A/660V

(OPTION)

FSU-W

Static Bypass Input

Fuse

200A/660V

280A/660V 280A/660V

F1,F2,F3 UPER-Y/UPFR-K

6.3A/250V 6.3A/250V

6.3A/250V 6.3A/250V

F1 CABR-JA

12A/600V