Failure Code List

Note 1

Note 2

Note 3

LCD Failure Code

Status

Guidance

Buzzer

External send-

out contact

Failure LED

00

Test mode (Pulse check)

-

[1]

-

-

01

Maintenance mode

-

[1]

-

-

10

Battery circuit abnormal

Call service engineer

[1]

Minor

Flicker

11

Battery test

-

-

-

-

12

Battery circuit abnormal

Call service engineer

[1]

Minor

Flicker

13

Battery depleted warning

-

[1]

Alarm

Flicker

14

Battery depleted

-

[2]

Alarm

Lit up

15

Battery temperature abnormal

Check battery

[1]

Alarm

Flicker

16

Battery temperature abnormal

Check battery

[1]

Minor

Flicker

17

Battery charge voltage abnormal

Call service engineer

[1]

Alarm

Flicker

18

DC voltage abnormal

Call service engineer

[1]

Minor

Flicker

19

Battery depleted (Converter
overload)

Check AC input voltage

[2]

Major

Lit up

21

AC input voltage out of range

Check AC input voltage

[1]

Alarm

-

22

AC input phase rotation error

Check AC input voltage

[1]

Minor

Flicker

23

Converter overload

Call service engineer

[1]

Alarm

Flicker

24

Converter over current

Call service engineer

[1]

Minor

Flicker

25

Converter abnormal (DCOV)

Call service engineer

[2]

Major

Lit up

26

Converter abnormal (DCUV)

Call service engineer

[2]

Major

Lit up

27

Converter abnormal

Call service engineer

[2]

Major

Lit up

28

Converter abnormal at pre-charge

Call service engineer

[2]

Major

Lit up

31

Inverter voltage abnormal

Call service engineer

[1]

Minor

Flicker

32

Inverter abnormal (VLOV)

Call service engineer

[2]

Major

Lit up

33

Inverter abnormal (VLUV)

Call service engineer

[2]

Major

Lit up

34

Inverter abnormal (OC)

Call service engineer

[2]

Major

Lit up

35

Inverter abnormal

Call service engineer

[2]

Major

Lit up

36

52C abnormal

Call service engineer

[1]

Minor

Flicker

37

52C abnormal

Call service engineer

[1]

Minor

Flicker

41

Bypass voltage out of range

Check bypass input

-

Alarm

Flicker