Installation Procedure

24

Installation of indoor unit

Each air return and supply duct should fix to the floor precast slab by using an iron stand. Use glue to
seal the interface closely. Recommend the distance between the air return duct and the wall is more than
150mm.

The distance between air duct outlet and air conditioner outlet is according to the length of actually installed
air duct and in service behavior of the static pressure terminal: Installation sketch map for long and short air
duct is showed below, when connect to short air duct, using low static terminal (terminal color is write), the
distance between air duct outlet and air conditioner outlet is no more than 0.5m; when connect to long air duct,
using middle static terminal (terminal color is red), the distance between air duct outlet and air conditioner outlet
could be within 5m at this point.

When installing the ceiling concealed type indoor unit, a specially designed return air
bellows shall be installed, as shown in Figure 3, Figure 4.

A

Installing building roof

Ceiling

Air supply

Air outlet duct

Unit

Return air

Return air bellows

Figure 3

Detail A

Figure 5

M8 broad foundation bolt

M8 suspension screw

M8 broad lock ring

M8 nut

Unit

Air outlet grille

Air supply

No obstacles
within 1 m

Unit

Return air

Return air bellows

*0.5m or*5m

As figure shown, suspend and install the unit.

Drain piping of condensed water should keep a downhill grade of 1% or more. Use insulating pipe to cover
the drain piping of condensed water to keep warmth.

Figure 4

air return shutter

air return duct

sling dog

drain piping

transition
air duct

air outlet

duct

air diffuser

joint of air diffuser

Figure 5

Figure 6