Users Manual & Installation Guide

PV- 1800: Power supply module with GSM MODEM

Page 13 / 19

Internal registers

Address

Access

Name

Function

Base+0

Read only

REG_SIGN

Signature (8Ch)

Base+1

Read only

REG_MODEL

Model

Base+2

Read/write

REG_DIGOUT

Digital outputs

Base+3

Read only

REG_DIGIN

Digital inputs

Base+4

Read only

REG_CNTLO

Counter LSB

Base+5

Read only

REG_CNTHI

Counter MSB

Base+6

Read/write

REG_CNTMODE Counter configuration

Base+7

Read/write

REG_MODEM

Modem status and on/off command

Base+8

Read/write

REG_UPS

UPS status

Base+9

Read/write

REG_UPSSHDN Delayed UPS shutdown

Base+0Ah Read/write

REG_ADCLO

ADC command/result LSB

Base+0Bh Read/write

REG_ADCHI

ADC result MSB

Base+0Ch -

reserved

Base+0Dh -

reserved

Base+0Eh -

reserved

Base+0Fh -

reserved

REG_SIGN (base+0): Signature (read only)

Always reads 8Ch. Can be used by software to verify the presence of the PV-1800.

REG_MODEL (base+1): PV-1800 firmware model number (read only)

When the firmware is changed to remove, add, or change features, the model number is

changed. Current model number is 00h.

REG_DIGOUT (base+2): Digital outputs (read/write)

Writing to bit 0-6 sets digital output 0-6. 0=off, 1=on.

Reading bit 0-6 returns the current status of digital output 0-6.

Bit 7 is always 0.

REG_DIGIN (base+3): Digital inputs (read only)

Reading bit 0-7 returns the current status of digital input 0-7. 0=off, 1=on.

DI0 and DI1 can also be used as counter inputs. Regardless of this, their current

status can always be read at this register.

REG_CNTLO (base+4): Counter low byte (read only)

Reading this register returns bit 0-7 of the current value of the counter, and

simultaneously stores bit 8-15 of the counter in the REG_CNTHI register.

REG_CNTHI (base+5): Counter high byte (read only)

Reading this register returns the previously stored value of bit 8-15 of the

counter.