4-12. Electrical Service Guide

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-

tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.

50/60 Hertz Models

Input Voltage

230

380

400

440

460

575

Input Amperes At Rated Output

57

34

33

30

29

23

Max Recommended Standard Fuse Rating In Amperes

1

Time-Delay

2

70

40

40

35

35

25

Normal Operating 3

90

50

50

45

40

35

Min Input Conductor Size In AWG

4

6

8

8

10

10

10

Max Recommended Input Conductor Length In Feet (Meters)

145 (44)

256 (78)

284 (86)

226 (69)

243 (74)

380 (116)

Min Grounding Conductor Size In AWG

4

8

10

10

10

10

10

Reference: 2005 National Electrical Code (NEC)

1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” .

3 “Normal Operating” (general purpose − no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

4-13. Placing Jumper Links

Ref. 800 103-A

!

Disconnect and lockout/tag-

out input power before

installing or moving jumper

links.

Check input voltage available at

site.
1

Jumper Link Label

Check label.
2

Jumper Links

Move jumper links to match input

voltage.
Close access door, or go on to

Section 4-14.

Tools Needed:

1

3/8 in

3/8 in

L1(U)

S−174973−B

GND/PE

3

Connect

GND/PE

Conductor

First.

Input

Contactor

L2(V)
L3(W)

230VOLTS

460VOLTS

575VOLTS

Donot

overtighten

jumperlinknuts.

2