4 prerequisites to instal, 5 general description 1-3, 1 electrical specificati – MGE UPS Systems 100 User Manual

Page 11: Installation and user manual

Advertising
background image

Introduction

page 1 — 3

Installation and User Manual

1.4

Prerequisites to Installation

An efficient installation depends on careful planning and site preparation. Installation of the equipment must be han-
dled by skilled technicians and electricians familiar with the special requirements of high-voltage electrical equip-
ment. The installation must comply with the requirements of the National Electrical Code (ANSI/NFPA 70, latest
issue) and local codes as applicable, and safety standard, UL1012 listed; ul1449 compliant; meets FCC Cat. A.

1.5

General Description

The overall function of the Topaz 100 Ultra-Isolator is to attenuate transients and noise that originate on the

incoming power lines and provide a newly derived, isolated power source.

The Topaz 100 Ultra-Isolators are used to protect sensitive electronic equipment and computers from power line

noise and transients. There are common disturbances on the power lines caused by lightning, motor starting and

stopping, utility network switching and general electrical noise, which will adversely affect sensitive electronic

equipment, especially computers.

The Topaz 100 Ultra-Isolator utilizes a unique method of shielding and isolation which provides low capacitive

coupling between input and output circuits. This low capacitance, together with a highly effective filter circuit, results

in ultra high common mode and normal mode noise attenuation.

1.5.1

Electrical Specifications

Input voltage

120, 240, 480VAC – depending on model

Common mode noise attenuation

140dB @ 100KHz

Normal mode noise attenuation

65dB @ 100KHz

Overload capacity

600% for 1 cycle, 300% for 30 seconds

Dielectric strength

2500 VAC minimum

Frequency

60Hz ± 5%

Impedance

3% to 6%, depending on size

Efficiency

93% to 97%, depending on size

Input voltage range

Nominal voltage ± 10%

Load regulation

2% to 5%, no load to full load at unity power factor

Harmonic distortion

Adds less than 1% THD, under linear loading

Coil insulation

200ºC

Temperature Rise

115ºC max rise above a 40ºC ambient

Electro-magnetic interference

Less than 0.2 gauss @ 3 ft.

1.5.2

Environmental Specifications

Audible noise

Less than 50dB measured @ 3ft.

Operating temperature

0 to 40º C

Storage temperature

-20º to +50º C

Operating altitude

5,000 ft. (without derating)

Operating humidity

95% relative (non-condensing)

Advertising