3: circuit diagram for 125va-10, Topaz 100 ultra-isolator transformer – MGE UPS Systems 100 User Manual

Page 20

Advertising
background image

Figure 2-3: Circuit Diagram for 125VA-1000VA 240/120VAC Input.

Installation

Topaz 100 Ultra-Isolator Transformer

page 2 — 4

X1

X3

X2

X4

G

H1

H1-A

H3

H2

H4

H1

H1-A

H3

H2

H4

X1

X3

X2

X4

G

240V

INPUT

120V

INPUT

LINE

NEUTRAL

GROUND

LINE

* NEUTRAL

GROUND

120V

OUTPUT

240V

OUTPUT

LINE

LINE

LINE

LINE

T1

FIL

TER BOARD

IL

IN

L

N

LOAD

F1

SHIELD

OUTPUT

HARDWIRE CONNECTION DIAGRAM

240/120V

AC OUTPUT

60Hz

GROUND STUD

(BOTT

OM OF ENCLOSURE)

NOTE: UNIT

F

ACT

OR

Y

WIRED FOR 120V

AC INPUT

AND OUTPUT

.

CHANGING FROM

AN INPUT

OF 120V

AC

T

O

AN INPUT

OF 240V

AC

ON MODELS RA

TED

A

T

1000V

A

AND BELOW

, REQUIRES

THA

T

THE

INPUT

FUSE BE CHANGED

AS INDICA

TED.

A

FUSE RA

TED

A

T

240V

AC

AND

THE CORRECT

AMPERAGE HAS BEEN PROVIDED WITH

THE

T

O

P

AZ 100.

15

2

6

3

7

4

8

CORE

* NEUTRAL

(OR LINE IF X4-G JUMPER IS REMOVED.

SEE NOTE

A

T

BOTT

OM OF P

AGE.)

NOTE: IF

YOU DESIRE

T

O

HA

VE

THE OUTPUT

NEUTRAL

UNGROUNDED,

THE BONDING JUMPER CONNECT

OR BETWEEN OUPUT

TERMINAL

X4

AND GROUND MA

Y

BE REMOVED. NOTE HOWEVER,

THA

T

THIS WILL

SIGNIFICANTL

Y

REDUCE

THE COMMON-MODE NOISE

A

TTENUA

TION

OF

THE UL

TRA-ISOLA

T

OR. REMOVING

THIS BOND WILL

ALLOW FOR 240V

AC LINE

T

O

LINE

APPLICA

TIONS

AND PEOVIDE ISOLA

TION.

#16 A

W

G

#16 GREEN

GROUND

GROUND

LUG

RA

TING

F1

(120V)

F1

(240V)

250V

A

500V

A

750V

A

1000V

A

250V

3A

250V

1.5A

250V

6A

250V

3A

250V

12A

250V

6A

250V

8A

250V

4A

Recommended

Minimum Wire Size

# 14 GA.

# 14 GA.

# 14 GA.

# 14 GA.

# 16

# 16

# 16

# 16

WIRE

SIZE

125V

A

250V

1.5A

250V

.75A

# 14 GA.

# 16

125V

A

- 1000V

A

240/120V

AC INPUT