English – Minuteman UPS UPS User Manual

Page 17

Advertising
background image

16

English

Default 120VAC / User selectable at 110, 120, 127VAC

3-6 years, depending on discharge cycles and ambient temp

700VA
500W

1000VA
700W

2000VA
1400W

1400VA
1000W

500 J

0 ns (instantaneous) normal mode; <5 ns common mode

<5%

0 to 40 degrees C (+32 to 104 degrees F)

Normal and common mode EMI/RFI suppression

2-12V7Ah

2-12V12Ah

2-12V17Ah

Audible noise at 1 m (3 ft.)

Electromagnetic immunity

<45 dBA

Storage elevation

Operating elevation

IEC 801-2 level IV, 801-4 level IV, 801 -5 level III

0 to +15,000 m (0 to +50,000 ft)

0 to +3,000 m (0 to + 10,000 ft)

Storage temperature

Operating temperature

-15 to +45 degrees C (+5 to +113 degrees F)

10 Base-T surge protection let-

through (as a percentage of

an applied +/-6 kV 1.2/50 us,

500 a 8/20 uS test)

Telephone line surge protec-
tion let-through (as a percent-
age of an applied +/-6 kV 1.2/
50 us, 500a 8/20 uS test)

Typical recharge time

Typical battery life

Battery type: Sealed, non-

spillable, maintenance free,

lead-acid

<1%

<5%

8 hours from total discharge

Noise filter

Surge voltage let-through (as

a percentage of an applied

ANSI C62.41 Cat. A +/-6 kV)

Surge response time

2-12V17Ah

Surge current capability

(one time, 8/20 uS waveform)

6500 Amps total

Surge energy rating (one time,

10/1000 uS waveform)

Protection

On-battery waveshape

Over current, short circuit protected and latching shutdown

True Sine Wave

On-battery frequency

50/60 Hz, +/-.5 Hz, unless synchronized to utility

On-battery output voltage

Maximum load

2-6 mS typical

50 or 60 Hz, +/-6Hz

Resettable circuit breaker

50 or 60 Hz, autosensing

0 - 165 VAC

80 - 150 VAC

110/120V Settings: 104-130 VAC, 127V Setting: 104-134 VAC

Transfer time

Frequency limits (AC Mode)

Input protection

Nominal input frequency

Output voltage (AC Mode)

Input voltage (on-line
operation)

Acceptable input voltage

S 2000

S 1400

S 1000

S 700

MODEL NUMBER

8.9 x 6.5 x 17.8" / 226.1 x 165.1 x 452.1 mm

38.6 (42)lb
17.5 (19)Kg

46.3 (50)lb
21 (22.5)Kg

61.7 (65)lb
28 (29.5)Kg

Weight - Net (Shipping)

Size - Net (Shipping)

67.2 (71)lb
30.5 (32)Kg

UL1778, UL497A, UL497B, cUL (CSA 22.1)

FCC Class B, CE certified

Safety and approvals

EMC Verification

FCC Class A, CE certified

H x W x D

(12.8 x 10.8 x 21.7" / 325.1 x 274.3 x 551.2 mm)

Advertising