<Initial start control timing chart>

Note 1: If the frequency of No. 1 compressor is above the specified level at the end of Step 2, the mode proceeds to

Step 3.

Note 2: At the completion of Step 2, if the frequency of No. 1 compressor is below the specified value and if Step 2 has

been completed less than 3 times, the process does not proceed to Step 3 but rather enters the Pause Step

and then repeats Step 2.

Note 3: At the completion of Step 2, if it has been completed more than 3 times, the mode will proceed to Step 3 even

if the frequency of No. 1 compressor is below the specified value.

30 minutes

Step 1

3

minutes

10 minutes

Step 2

5 minutes

Step 3

ON/OFF of

No.1 compressor

ON/OFF of

No.2 compressor

End of initial operation mode

Note 1

30 minutes

Step 1

3

minutes

10 minutes

Step 2

3

minutes

10 minutes

Step 2

Step 2

5 minutes

Step 3

Note 1

ON/OFF of

No.1 compressor

ON/OFF of

No.2 compressor

Note 2

End of initial operation mode

30 minutes

Step 1

3

minutes

10 minutes

Step 2

3

minutes

10 minutes

Step 2

3 times

3

minutes

10 minutes

Step 2

5 minutes

Step 3

Note 3

ON/OFF of

No.1 compressor

ON/OFF of

No.2 compressor

Note 2

End of initial operation mode

(Example 1)

(Example 2)

(Example 3)