–94–

No cooling

No heating

Check disconnection or looseness
of connectors.

Is there a problem?

Operate in cooling or heating (1 system
only when there are plural systems)

Cooling or heating

operation?

Heating operation

Note 1

Check if LEV 1 are fully open

LEV 1 fully open?

LEV3 are not

controlled

Check if LEV 1 are fully shut.

Yes

Note 2

No

Yes

No

Yes

No

Yes

No

Yes

Check if LEV3 is controlled by
superheat.

LEV3 is not controlled.

Check if SVM1 is ON.

SVM1 ON

Check if SVA, SVC are ON.

SVA, SVC ON

Check if SVB is OFF.

SVB OFF

Check if LEV 3 are controlled by
differential pressure.

Completion

Check SVB

Check SVA, SVC

Check SVM1

Check LEV3

Correct the problem.

Check LEV1

SVB ON

Check if SVB is ON.

SVA, SVC OFF

Check if SVA, SVC are OFF.

SVM1 OFF

Check if SVM1 is OFF.

LEV 1 fully shut?

Yes

No

Note 2

No

No

No

Yes

Yes

Yes

Note 3

Note 3

No

Yes

Yes

No

3) LEV, Solenoid Valve Troubleshooting Flow