B: compressor not running, no start attempt – Mermaid REFRIGERATION/FREEZER User Manual

Page 12

Advertising
background image

(3) Run all applicable tests before assuming Module or Compressor to be faulty.

B: Compressor Not Running, No Start Attempt.

Probable cause

Action

1

Supply voltage too low

Check voltage with a digital multi-meter
at the terminals on the Module. This
must be 11.7v or more for a 12v supply
& 24v or more for a 24v supply. Inspect
power supply, ground connections &
components for integrity. Check wire
sizing. Charge batteries if necessary.

2 Supply voltage too high

If a 12v supply is faulty & delivers over
17v, the compressor will not run. If it is
over 24v, it will assume that it is a 24v
supply & act accordingly.

3

Polarity incorrect

Check that the polarity is correct at the
Module.

4

Faulty thermostat

Remove the thermostat wires & jumper
the terminals that they were on together
temporarily. If the system then runs,
make the connection permanent &
control the system manually from the
breaker on your supply panel. Replace
thermostat as soon as possible.

5 Thermostat

wired

incorrectly, or faulty
connections.

Refer to the installation instructions &
confirm that connections are as they
should be. Ensure that the thermostat
connectors are pushed firmly on to the
Module terminals.

6 Multi-speed

board

incorrectly installed (if
fitted)

Check to make sure that the 2
connectors at the rear of the multi-speed
board are attached to the C & T
terminals of the Module.

7 Multi-speed

board

faulty

(if fitted)
** Optional Part **

Remove board & jumper terminals C &
T on the Module. Note; If the thermostat
wires are connected directly to C & T on
the Module, the compressor will run at
its slowest speed.

8

Compressor plug not

Disconnect the Module by removing the