16

Majestic Fireplaces

®

NVB Series B-Vent

7412950

Troubleshooting

FP396

Gas Supply On

• Supply Line Hooked up
• Shutoff Valve Open

NO

NO

NO

NO

• Lockout has engaged. Wait 60
seconds and try again.
• Piezo not tight enough for good
ground.
• For spark at electrode while
depressing Piezo (Red Button)
1/8" gap to pilot hood needed.
• All wiring connections
• Replace Piezo Ignitor
• Thermodisk

• For Air in the lines
• Thermopile needs a minimum
325mV. Adjust pilot flame height.
• All wiring connections
• Replace Thermopile
• Thermocouple needs a minimum
of 14mV.
• Defective valve. Turn to pilot,
meter should read greater than
100mV.
• Thermodisk

Pilot Lights with

Piezo Ignitor

YES

YES

YES

YES

Pilot Stays Lit

Pilot Lights Main

Burner

System OK

START

CHECK

• Wall switch is not turned on.
Watch for grounded wires!
• Thermopile needs a minimum
325mV
• Plugged burner orifice

Nova SIT 820 Standing Pilot