Troubleshooting, Majestic fireplaces, Nvb series b-vent – Majestic Appliances NVBC36 User Manual

Page 17

Advertising
background image

17

Majestic Fireplaces

®

NVB Series B-Vent

7412950

FP649

• Turn gas supply off
• Turn ON/OFF Switch
to call for heat.

NO

NO

NO

NO

NO

NO

NO

Spark across

Ignitor Sensor gap

Power to module

(24V nominal)

YES

YES

YES

YES

YES

YES

YES

• Turn gas on

Pilot burner lights?

Spark stops when pilot

is lit?

Main Burner lights?

• Replace Module

START

• Line Voltage (120VAC)
• Low Voltage Transformer
(19.5 minimum VAC)
• ON/OFF Switch
• Wiring connections
• Thermodisk

• Check continuity of ignition cable and ground wire.
• Clean flame rod.
• Check electrical connections beween flame rod and module.
• Check for cracked ceramic flame rod insulator.
• Check that pilot flame covers flame rod and is steady blue.
• Adjust pilot flame.
• If problem persists, replace module.

Unplug Ignition Lead

and check spark

at module

(24VAC nominal)

Spark OK?

• Check ignition cable, ground wiring, Ceramic Insulator and gap. Correct as necessary
• Check boot of ignition cable for signs of melting or buckling. Take protective
actions to shield cable and boot from excessive temperatures.

• Check for 24VAC across MV-MV/PV terminals. If no voltage, replace module.
• Check electrical connections between module and gas control. If okay, replace gas
control or gas control operator.

• Check for continuity of igniton cable and ground wire. NOTE: If ground is poor or
erratic, shutdowns may occur occasionally even though operation is normal
at time of checkout.
• Check that the pilot flame covers flame rod and is steady and blue.
• If checks are okay, replace module.

Troubleshooting

Ends

• Check that all manual gas valves are open, supply tubing and pressures are good,
and pilot burner orifice is not blocked.
• Check electrical connections between module and pilot operator on gas control.
• Check for 24VAC across PV-MV/PV terminals on module. If voltage is okay, replace
gas control. If not, replace module.

NOTE: If S8600B goes into lockout, reset system.

NOTE: If S8600B goes into lockout, reset system.

CHECK :

System runs until

ON/OFF switch is in

"OFF" position

Troubleshooting

Remove glass panel before servicing.

NOVA SIT 822 with Honeywell S8600 B Electronic Ignition