4-12. Electrical Service Guide

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-

tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.

60 Hz

Input Voltage

230

460

575

Input Amperes At Rated Output

180

90

72

Max Recommended Standard Fuse Rating In Amperes

1

Time-Delay

2

225

110

90

Normal Operating

3

250

125

110

Min Input Conductor Size In AWG

4

3/0

3

4

Max Recommended Input Conductor Length In Feet (Meters)

204

(62)

337 (103)

438 (134)

Min Grounding Conductor Size In AWG

4

4

6

6

Reference: 2005 National Electrical Code (NEC)

1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” .

3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

4-13. Placing Jumper Links

Ref. 802 295

Tools Needed:

3/8 in

2

Do not overtighten

jumper link nuts.

1

!

Disconnect and lockout/tag-

out input power before

installing or moving jumper

links.

Check input voltage available at

site.
1

Jumper Link Label

Check label − only one is on unit.
2

Jumper Link

Move jumper links to match input

voltage, and label on unit.
Close and secure access door, or

go on to Section 4-14.