2. Installation

2.5 Connections with a FlexPDU (Power Distribution Unit) module (optional)

2.6 Connections with a HotSwap MBP module (optional)

The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads
(HotSwap function).

1 - Connect the UPS socket (10) to the AC-
power source using the cable (31) supplied.

2 - Connect the input socket on the FlexPDU
module (48) to the UPS outlet (7) using the
cable (41) supplied. The cable and the
connectors are marked in red.

3 - Connect the equipment to the outlets (45),
(46)
and (47) on the FlexPDU module. These
outlets differ, depending on the version of the
FlexPDU module.

4 - Fit the connection securing system that
prevents the plugs from being pulled out
accidentally.

1 - Connect the input socket (56) on the
HotSwap MBP module to the AC-power
source using the cable (31) supplied.

2 - Connect the UPS input socket (10) to the
"UPS Input" (55) on the HotSwap MBP
module, using the cable (44) supplied. These
cables and the connectors are marked blue.

3 - Connect the UPS outlet (7) to the "UPS
Output" (54) on the HotSwap MBP module,
using the cable (44) supplied. These cables
and the connectors are marked red.

4 - Connect the equipment to the outlets (49)
and (50) on the HotSwap MBP module.
These outlets differ, depending on the
version of the HotSwap MBP module.

Caution. Do not use UPS outlets (8) and (9)
to supply equipment because use of
switch (53) on the HotSwap MBP module
would cut supply to the equipment. It is
advised not to remove the protective film
from outlets (8) and (9).

7

8

9

10

48

47

46

45

FlexPDU

41

31

7

8

9

10

By-p

ass

Normal

UPS ON - OK to switch

BY

P

ASS SWITCH

56

55

49

HotSwap MBP

50

54

53

51 52

44

31