4. Access to measurements and personalisation data

Output personalisation

(1) These parameters may be modified only when the UPS is OFF.
Detailed comments are available in the Personal Solution-Pac software.

ON/OFF personalisation

Battery personalisation

4.4 Personalisation using external software

Function

Factory setting

Other available settings

Comments

Output voltage

(1)

230 Volts AC

200/208/220/240 Volts AC

Frequency converter

(1)

Disabled

Enabled

The connected devices are never
transferred to the bypass.

Output frequency

(1)

Automatic selection

50 or 60 Hz

User selectable only if the
frequency-converter function is
enabled.

Transfer to the bypass AC
input

(1)

Bypass AC power must
be within tolerances

Bypass AC power may be
outside tolerances

Overload level

(1)

102%

50 / 70%

Alarm if threshold is overrun.

Function

Factory setting

Other available settings

Comments

Start on battery power

Enabled

Disabled

Automatic restart

Enabled

Disabled

The UPS restarts automatically when
AC power returns.

Energy savings

Disabled

Enabled

When function enabled, battery shuts
down when power drops to <5%.

Detection of phase/
neutral inversion (SWF)

Disabled

Enabled

When function enabled, the UPS
remains OFF if the system detects
phase/neutral inversion.

Function

Factory setting

Other available settings

Comments

Battery test

Weekly test

No test / daily test /
monthly test

Low-battery warning

20%

0 to 100%

Adjustable in 1% steps.

Selection of the backup
time

Automatic detection of
number of battery
modules

65 to 400 Ah

Battery protection against
excessive discharges

Enabled

Disabled

When function disabled, MGE UPS
SYSTEMS warranty no longer
applies.

Insert the Solution-Pac CD-ROM in the drive.

On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal

Solution-Pac software.

Then select "Settings", "Advanced settings" and "UPS settings".

Note that the Linux/Unix/MacOS versions of the Personal Solution-Pac software do not offer this possibility.