Operation, 5 shutdown, Output" tab "bypass" tab – MGE UPS Systems EX 1500 User Manual

Page 20

Advertising
background image

Page 20 -

51031604EN/AB

3. Operation

bypass

Personalisable function

Rated UPS voltage

Rated UPS frequency

UPS tolerance for AC-power

source frequency

Overload alarm threshold

UPS restart following short-circuit

Default setting

230 V

F = 50 Hz

F

±

5%

110%

Disabled

Options

200 V - 210 V - 220 V - 240 V

60 Hz

F

±

1% to

±

10%, in 1% steps

0 to 110%, in 10% steps

Enabled (click to add check)

Personalisable function

Transfer to bypass if overload

Transfer to bypass following a fault, whatever the

conditions on the AC-power source

Default setting

Enabled

Disabled

Options

Disabled (click to remove check)

Enabled (click to add check)

"Output" tab

"Bypass" tab

3.5 Shutdown

23

Press button 23 (return to the OFF position).

The connected equipment is no longer supplied with power.