Maintenance, 2 replacement of the battery module, Tower model – MGE UPS Systems EX 1500 User Manual

Page 23

Advertising
background image

51031604EN/AB

- Page 23

A

B

A

F

G

C

D

E

4.2 Replacement of the battery module

4. Maintenance

Removal of battery module

A - Press to open door.
B - Slide the door open and remove it.
C D E - Procedure to remove the protective cover.
F - Disconnect the battery module.
G - Remove the battery module.

Tower model

Safety rules:

Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be
taken for all handling:

remove all watches, rings, bracelets and any other metal objects;

use tools with insulated handles.

Reinstallation of the battery module

Carry out the above operation in reverse order.

To maintain an identical level of performance and safety, use a battery module identical to that previously mounted in the

UPS.

Press the two parts of the battery connector tightly together to ensure proper connection.