battery replacement

ESV8+

Rack / 11+Rack /

14+

Rack /22+Rack

see important battery safety rules

(see page i);

batteries can be replaced without risk, but

don't hesitate to contact our after sales
department to confirm battery failure, and to
give you further information;

battery replacement can be performed

with UPS on utility power, but we
recommend you to switch off the unit in
order to avoid any data loss;

use a screwdriver to remove the cover on

the right side of the UPS ESV+

Rack;

use a screwdriver to remove horizontal

metal plate holding the batteries.

For ESV22+

Rack remove terminal before

removing the battery.

pull out battery block using tapes on the

sides;

disconnect battery wires red (+) and black

(-) from the UPS on battery terminals;

replace all batteries with new batteries,

same voltage and same rating (Volts, Ah),
then connect battery wires again (sparks
may occur during connection);

push battery block back in, screw metal

front panel on, then click plastic front panel
into place and secure the plastic plate with
screws.

+

+

!

%

%

1

2

+

+

!

%

%

1

2

+

+

!

%

%

1

2