PAGE 34 — DCA25SSIU3 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (12/20/10)

GENERATOR SHUT-DOWN PROCEDURES

2. Let the engine cool by running it at low speed for 3-5

minutes with no load applied.

3. Place the ignition switch (Figure 52) in the “STOP

position, remove the key and store in a safe place.

Figure 52. Ignition Switch (Stop Position)

4. Remove all loads from the generator.

5. Inspect entire generator for any damage or loosening of

components that may have occurred during operation.

EMERGENCY SHUTDOWN PROCEDURE

1. Turn ignition switch key to the STOP position.

2. To shut-down the engine in the event of an emergency,

switch the MAIN, GFCI and LOAD (Figure 51) circuit
breakers to OFF position.

AUTOMATIC SHUT-DOWN SYSTEM

This unit is equipped with safety devices to automatically
stop the engine in the event of low oil pressure, approximately
14 psi (97 kPa), or high water temperature, approximately
230° F (110° C). The alarm lamps on the Engine Control
Panel illuminate to signify the reason for the shutdown.

NOTICE

Before inspecting, turn the ignition switch to the STOP
position, place all circuit breakers in the OFF position
and allow suffi cient time for adequate cooling. When
ready to restart, complete all steps in the Generator
Startup Procedure section of this manual.

12. Place the main, GFCI, and aux. circuit breakers in the

ON position (Figure 49).

Figure 49. Main, Aux. and GFCI

Circuit Breakers (ON)

13. Observe the generator’s ammeter (Figure 50) and

verify it reads the anticipated amount of current with
respect to the load. The ammeter will only display a
current reading if a load is in use.

Figure 50. Ammeter (Load)

14. The generator will run until manually stopped or an

abnormal condition occurs.

NORMAL SHUTDOWN PROCEDURE

To shutdown the generator, use the following procedure:

1. Place both the MAIN, GFCI and LOAD circuit breakers

as shown in Figure 51 to the OFF position..

Figure 51. Main, GFCI and Load

Circuit Breakers Off

WARNING

NEVER stop the engine suddenly except in an
emergency.