Murphy Automatic Engine Controller A88-F User Manual

Page 12

Advertising
background image

Terminal 1: Crank (source)

Diagram 4: A88-F Wiring Terminals

Terminal 2: Crank (sink)

Terminal 3: Choke (sink)

Terminal 4: Start I/P

Terminal 5: Breaker ignition I/P

Terminal 6: Magnetic pickup I/P

Terminal 21: Common

Terminal 22: Normally Closed (N.C.)

Terminal 23: Normally Open (N.O.)

Terminal 24: No Connection

Terminal 25: Negative (–)

Terminal 26: Positive (+)

Terminal 7: Alternator I/P

Terminal 8: Vacuum switch I/P

Terminal 9: Ground for time delay I/P

Terminal 10: No connection

Terminal 11: Oil pressure I/P

Terminal 12: Water temperature I/P

Terminal 13: Spare I/P

Jumper for alarm
before start

Terminal 14:

Terminal 15:

Terminal 16: Connect to #17 for

momentary operation

Terminal 17: Stop I/P

Terminal 18: Engine running (sink)

Terminal 19: Time delay (sink)

Terminal 20: Alarm summary (sink)

23

26 25 24

Ignition Relay

22 21

1
2
3
4
5
6

7
8
9

10

11
12
13
14
15
16

17
18
19

20

9

Advertising