A. The Automatic Engine Controller, Model A88 and
A88-F
is designed to automatically start, monitor and stop
electric start engines. The A88 comes in an all-weather
case with a 5 foot cable and a plug for connection. The
A88-F is the same system, but housed in a panel-mount
case with terminals on back for connecting.

B. Features

1. Has a self-contained Auto-Off-Test Switch.
2. Rest and crank time selected by a single switch.
3. Adjustable crank disconnect speed switch.
4. Close a switch to run; open to stop feature.
5. Engine starts and runs when a contact closes and

stops when a separate set of contacts close.

6. Goes into a rest period in the event of a false start.
7. Alarm before start to alert personnel.

8. Crank disconnect circuitry accepts the following inputs:

a. breaker or electronic type ignition
b. magnetic pickup
c. alternator tach
d. flywheel alternator
e. mechanical switch

9. Has a built-in one minute time delay for customer use.
10. Five fixed crank attempts before shutdown.

SECTION I: INTRODUCTION

A. Power Requirements:

1. Voltage 8-30 VDC, negative ground.
2. Current @ 12 volts less load current.

a. standby

10 ma

b. crank

140 ma

c. shutdown

32 ma

3. Maximum fuse size, 4 amp, slow blow.

B. Input Requirements:

1. Start-stop control switch

a. SPST N.O. dry contact; close to run, open to stop

b. SPDT dry contact

c. Two SPST N.O. dry contacts; one, momentary

close to run; one momentary close to stop

2. Magnetic pickup or alternator tach requirements:

a. voltage 2 volts, rms minimum
b. 25 to 2000 hz crank disconnect
c. maximum 100 volts Pk Pk

C. Output Ratings: Source = switch to battery

Sink = switch to ground

1. Ignition or run relay; SPDT dry relay contacts

rated 10 amp @ 30 VDC resistive, 6 amp @ 30
VDC inductive.

2. Crank output

a. transistor

1 amp source

b. transistor

1 amp sink

3. Choke

a. transistor

1 amp sink

4. Time delay

a. transistor

1 amp sink

5. Summary

a. transistor

1/2 amp sink

11. An output to indicate that the engine is running

to be used as remote indication or in warm up
operation.

12. Has a summary of shutdown output.

13. Monitors the following engine functions and will

shut the engine down in event of a failure:

a. Overcrank
b. Oil Pressure
c. Engine Temperature
d. Spare

14. Has 30 second lockout feature for start up.
15. Output for choke actuator.

SECTION II: SPECIFICATIONS