Installation and user manual – MGE UPS Systems 40-150kVA User Manual

Page 21

Advertising
background image

Installation and User Manual

NOTES:

1. Total width, weight, and heat loss are for system line-up excluding battery cabinets.

2. Data does not include battery data; refer to the installation drawings supplied with your equipment.

Consult the installation drawings provided with your equipment.

1.3.1

AC Input Ratings

Voltage

480 VAC, + 12%, -15%

Frequency

60 Hz ± 4%

Phases

3 Ø (phase sequence must be A, B, C, clockwise)

Wires

3 wires plus ground (480-480 VAC only)

Power factor

Approximately 0.98 at full load

Current (on UPS/ on BYPASS) @ 480 VAC

40kVA

50kVA

65kVA

80kVA

100kVA

125kVA

150kVA

43A/48A

54A/60A

70A/78A

86A/96A

109A/120A

134A/150A

160A/180A

1.3.2

AC Output Ratings

Voltage (inverter only)

480 ± 1% VAC (steady-state conditions)

480 ± 5% VAC (transient conditions from 0% to 100% or 100% to 0%)

Frequency

60 Hz ± 0.1% (free-running)

Phases

3 Ø (phase sequence must be A, B, C, clockwise)

Wires

3 wires plus ground (480-480 VAC only)

Power factor

0.8

Current @ 480 VAC

40kVA

50kVA

65kVA

80kVA

100kVA

125kVA

150kVA

48A

60A

78A

96A

120A

150A

180A

Total harmonic
distortion (THD)

<2% (linear load)

<3% (for 100% non-linear load with a crest factor of less than 3.0)

Dynamic regulation

± 1% for balanced load
± 2.5% for 100% unbalanced load

Dynamic response

± 5% for 100% step load change

Overload

105% - 110% of rated current for 10 minutes

>110% - 130% of rated current for 1 minute

>130% - 150% of rated current for 10 seconds

>150% of rated current for 0.15 seconds

1.3.3

DC Ratings

Battery voltage (25° C)

float:

490 Vdc

nominal: 432

Vdc

minimum: 360

Vdc

Maximum Current at cut-off voltage

40kVA

50kVA

65kVA

80kVA

100kVA

125kVA

150kVA

96 ADC

120 ADC

154 ADC

189 ADC

235 ADC

294 ADC

353 ADC

System Description and Specifications

1 — 9

86-160310-00 E00