The Basic I/O 1

1-5(Vol.1)

DIGITAL OUTPUTS:
Digital output modules, commonly referred to as solid state relays, control external AC or DC
power sources. A dry-contact (mechanical relay) with very low contact resistance is also
available.

Digital output instruction types are:

Set outputs

Can set individual or multiple outputs On or Off.

Pulse Generator

Can generate 1 to 65,535, 50% duty cycle pulses whose equal
On and Off periods can range from 0.01 to 2.55 seconds.
Resolution can be reduced by a factor of 1-256 on a system
wide basis to increase the maximum pulse width available.

Modifiers:

One Shot

Can generate On or Off pulse durations of up to 10.9 minutes
with a resolution of 0.01 seconds. Resolution can be reduced by
a factor of 1-256 on a system wide basis increasing duration up
to 46 hours. Re-triggering is available.

Delayed

Can generate delayed On or Off outputs after delaying up to
10.9 minutes with a resolution of 0.01 seconds. Resolution can
be reduced by a factor of up 1-256 on a system wide basis
increasing the delay before changing state up to 46.6 hours. Re-
triggering is available.

Square wave

Can generate square waves with programmable On and Off
periods. On and Off periods have a base range from 0.01
seconds to 10.9 minutes. Resolution can be reduced by a factor
of 1-256 on a system wide basis increasing duration to 46.6
hours

.