TECHNICAL CHARACTERISTICS

2


1 TECHNICAL CHARACTERISTICS

1.1 GENERAL

The AX series steam boilers are type semi-fixed, horizontal smoke-tube type, complete with accessories.

The boilers are suitable for operation with pressurised burners for gas, fuel oil or heavy oil.
Safety, reliability, high efficiency and high quality saturated steam are the characteristics of our boilers.
Please consult the instructions with attention.

This high-pressure steam (12-15 kgf/cm

2

) generator uses a combustion chamber with flue gas inversion. For

operation at up to 3000 kg/h of steam generated there is partial exoneration (in Italy) in the employment of
specialist boiler operators. Local requirements as to personnel qualification MUST be taken into account for
the country where the unit is installed.

1.2 CHARACTERISTICS


Working pressure switches for operation (controlling the 1

st

and 2

nd

burner flame).


Locking pressure switches (stops the burner on reaching the maximum steam pressure; the boiler is

manually reset from the control panel).


Automatic level regulator (2 probes connected to an electronic conductivity relay maintain the water

level between the set levels).


Water level limits (2 probes connected to two independent electronic conductivity relays stop the burner

if the water level falls below the safe minimum; reset is manual on the control panel).