Electrical requirements – IPSO 120 User Manual

Page 18

Advertising
background image

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Tumblers – 120 and 170

4-08-45

17

Electrical Requirements

Refer to Table 5.

NOTE: Minimum wire sizes are obtained from

Canadian Electrical Code and are intended for use

as a guideline only. Electrical connections should be

made only by a qualified electrical contractor in

accordance with all applicable local and national

requirements.

NOTE: Electrical specifications below are subject

to change without notice. Always refer to product

serial plate for most current specifications of

product being installed.

NOTE: Use copper conductors only.

NOTE: 3 Phase Only– Each tumbler must be

connected to its own individual branch circuit

breaker, not fuses, to avoid the possibility of “single

phasing” and causing premature failure of the

motor(s).

For 120 Pound Tumbler Models

Serial Plate Rating

Terminal Block

Connections Required

Rated

Current*

Breaker

Rating

Breaker

Poles

Recommended

Wire Size

208-230V/60Hz/3ph

L1, L2, L3 and ground

7.7

15 Amps

3

14 AWG (2.08 mm

2

)

380-415V/50Hz/3ph

L1, L2, L3 and ground

3.8

10 Amps

3

14 AWG (2.08 mm

2

)

380V/60Hz/3ph

L1, L2, L3 and ground

4.1

10 Amps

3

14 AWG (2.08 mm

2

)

440V/60Hz/3ph

L1, L2, L3 and ground

3.8

10 Amps

3

14 AWG (2.08 mm

2

)

460-480V/60Hz/3ph

L1, L2, L3 and ground

3.9

10 Amps

3

14 AWG (2.08 mm

2

)

* Current ratings vary slightly depending on model; refer to serial plate.

For 170 Pound Tumbler Models

Serial Plate Rating

Terminal Block

Connections Required

Rated

Current*

Breaker

Rating

Breaker

Poles

Recommended

Wire Size

208-230V/60Hz/3ph

L1, L2, L3 and ground

13.5

20 Amps

3

12 AWG (3.31 mm

2

)

380-415V/50Hz/3ph

L1, L2, L3 and ground

6.9

15 Amps

3

14 AWG (2.08 mm

2

)

380V/60Hz/3ph

L1, L2, L3 and ground

6.6

15 Amps

3

14 AWG (2.08 mm

2

)

440V/60Hz/3ph

L1, L2, L3 and ground

6.4

15 Amps

3

14 AWG (2.08 mm

2

)

460-480V/60Hz/3ph

L1, L2, L3 and ground

6.7

15 Amps

3

14 AWG (2.08 mm

2

)

* Current ratings vary slightly depending on model; refer to serial plate.