Fire safety requirements, Fire suppression, Fire suppression equipment – Juniper Networks M5 User Manual

Page 61

Advertising
background image

Fire Safety Requirements

Description

Tolerance

Temperature

Normal operation ensured in temperature range of 32° F to
104° F (0° C to 40° C)

Seismic

Designed to meet Bellcore Zone 4 earthquake requirements

Install the router only in restricted areas, such as dedicated equipment
rooms and equipment closets, in accordance with Articles 110-16, 110-17,
and 110-18 of the National Electrical Code, ANSI/NFPA 70.

For additional safety guidelines and requirements, see “Safety and
Regulatory Compliance Information” on page 129.

Fire Safety Requirements

In the event of a fire emergency involving routers and other network equipment, the safety
of people is the primary concern. You should establish procedures for protecting people in
the event of a fire emergency, provide safety training, and properly provision fire-control
equipment and fire extinguishers.

In addition, you should establish procedures to protect your equipment in the event of a fire
emergency. Juniper Networks products should be installed in an environment suitable for
electronic equipment. We recommend that fire suppression equipment be available in the
event of a fire in the vicinity of the equipment, and that all local fire, safety, and electrical
codes and ordinances be observed when installing and operating your equipment.

Fire Suppression

In the event of an electrical hazard or an electrical fire, you should first turn power off to
the equipment at the source. Then use a Type C fire extinguisher, which uses noncorrosive
fire retardants, to extinguish the fire. For more information about fire extinguishers, see
“Fire Suppression Equipment” on page 41.

Fire Suppression Equipment

Type C fire extinguishers, which use noncorrosive fire retardants such as carbon dioxide
(CO2) and Halotron™, are most effective for suppressing electrical fires. Type C fire

extinguishers displace the oxygen from the point of combustion to eliminate the fire.
For extinguishing fire on or around equipment that draws air from the environment for
cooling, you should use this type of inert oxygen displacement extinguisher instead of an
extinguisher that leave residues on equipment.

Do not use multipurpose Type ABC chemical fire extinguishers (dry chemical fire
extinguishers) near Juniper Networks equipment. The primary ingredient in these fire
extinguishers is monoammonium phosphate, which is very sticky and difficult to clean.

Prepare for Router Installation

41

Advertising
This manual is related to the following products:

M10