13 dya coil delta p vs. airflow, 13 superheat charging table for dya036 – Johnson Controls 341426-BIM-A-0108 User Manual

Page 19

Advertising
background image

341426-BIM-A-0108

Johnson Controls Unitary Products

19

FIGURE 13 - DYA COIL DELTA P VS. AIRFLOW

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

400

600

800

1000

1200

1400

1600

1800

2000

2200

Airflow (CFM)

ID Coil De

lta

P

DYA042

DYA Coil Delta P vs Airflow

DYA048 - 060

DYA036

DYA036

DYA042

DYA048-060

TABLE 13: SUPERHEAT CHARGING TABLE FOR DYA036

OUTDOOR

TEMP. °F

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM

INDOOR WB TEMP. (°F)

55

57

59

61

63

65

67

69

71

73

75

65

27.1

28.4

29.7

31.1

32.4

33.7

35.0

35.9

36.8

37.6

38.5

70

23.3

24.8

26.2

27.7

29.2

30.6

32.1

33.5

34.9

36.4

37.8

75

19.5

21.1

22.7

24.4

26.0

27.6

29.2

31.2

33.1

35.1

37.1

80

15.7

17.5

19.2

21.0

22.8

24.5

26.3

28.8

31.3

33.8

36.3

85

11.9

13.8

15.7

17.6

19.6

21.5

23.4

26.5

29.5

32.6

35.6

90

8.6

10.6

12.6

14.6

16.6

18.6

20.6

24.1

27.6

31.1

34.6

95

5.3

7.4

9.5

11.5

13.6

15.7

17.8

21.7

25.7

29.7

33.7

100

-

5.6

7.6

9.6

11.6

13.6

15.6

20.1

24.5

28.9

33.4

105

-

-

5.7

7.6

9.6

11.5

13.5

18.4

23.3

28.2

33.1

110

-

-

-

5.6

7.5

9.4

11.3

16.7

22.1

27.4

32.8

115

-

-

-

-

5.5

7.4

9.2

15.0

20.9

26.7

32.5

Advertising