Rack-mounted installation, Rack-mounted installation -6, Figure 2-5 – Juniper Networks ERX-1410 User Manual

Page 42

Advertising
background image

CHAPTER 2
Installing the ERX System

2-6

Figure 2-5 ERX-700 series rear view

Rack-Mounted Installation

We recommend that you use a standard EIA distribution rack. Refer to

Rack Requirements

in

Appendix D, Preparing Your Site

, for detailed

rack information. Before installing the systems in the rack, consider the
following guidelines:

You can install up to three ERX-1400 series systems in a single 84-inch
rack.

Installing multiple systems in a single rack allows you to maximize
your available space. An ERX-1400 series system has a plenum that
allows air to circulate between systems.

You can install an ERX-1400 series system and an ERX-700 series
system together in the same rack.

If you install an ERX-700 series system above an ERX-1400 series
system in the same rack, you must install a plenum between the
ERX-700 series system and the ERX-1400 series system so that the air
can circulate between the systems. See

Figure 2-6

. This plenum is

available from Juniper Networks.

If you install an ERX-1400 series system above an ERX-700 series
system, there is no need to install a plenum between the units because
the ERX-1400 series system has one at its base.

OC3 I/O

connectors

CT3 I/O

connectors

Fast Ethernet

connector

Console

connector

Power

connectors

SRP I/O

connectors

Power input

module