4 central shutdown configuration – Schneider Electric 66123 User Manual

Page 46

Advertising
background image

Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 46/98

Network Management Teleservice Card

APC by Schneider Electric

www.apc.com

6.4.4 Central shutdown configuration

The menu Shutdown Parameters is not present with a UPS Static Switch Cabinet.

Click on "Notified Applications" in the menu, then "Configuration".

This page is used to define either the "shutdown" or the "notification" settings used by the Network Shutdown Modules that connect to Network

Management Card. These settings are used by the Network Shutdown Modules if they are in central-configuration mode or if their configuration

is not valid.

Shutdown duration: the shutdown duration necessary to properly shutdown the computer.

Shutdown after: the time available to the user from the power failure until the launch of the shutoff sequence of the UPS and equipment. This

parameter is optional. Uncheck the box if you wish not to use this parameter.

Broadcast : Sends network notifications to the Administrators and Users groups on events declared in the server hosting the NSM

If you wish to set up a new configuration for the Network Shutdown Modules already set to "central-configuration mode", proceed as indicated

below:

Change the Network Shutdown Module parameters in the "Notified Applications" page.

Click the "Save" button.

In this page, select the NSMs for which you want to apply the new configuration.

Press the "Remove" button.

The NSMs selected will disconnect then reconnect and use the new configuration.