Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 72/98

Network Management Teleservice Card

APC by Schneider Electric

www.apc.com

10.1.3 Configuration of the JBUS/MODBUS communication parameters

Connect the card to a computer equipped with a Hyper terminal type emulator. The serial link must be set at 9600 baud, 8 bits, no parity, 1 stop

bit, and without flow control.

Check that UPS power is on.

Enter the MGEUPS or mgeups password (non modifiable).

The next menu appears:

-----------------------------------------------------------------------------

MGE UPS SYSTEMS

NETWORK MANAGEMENT CARD

-----------------------------------------------------------------------------

1 : Reset

2 : Network configuration

3 : Set Login Password to Default

4 : Return to Default Configuration

5 : Jbus configuration

6 : Sensor configuration

0 : Exit

-----------------------------------------------------------------------------

Type 5 and return to display the JBUS configuration menu.

The next menu appears:

-----------------------------------------------------------------------------

Jbus settings

-----------------------------------------------------------------------------

1 : Display Jbus settings

2 : Modify Jbus settings

3 : Display Jbus diagnostics

4 : Reset Jbus diagnostics

5 : Return to Jbus Default Configuration

6 : Display Jbus frames

0 : Exit

-----------------------------------------------------------------------------